Environmental Engineering Reference
In-Depth Information
TABLE   9.2
Electrically Operated Unitary and Applied Heat Pumps, Minimum Eficiency Requirements
Heating Section
Type
Subcategory or Rating
Conditions
Minimum
Efficiency
Equipment Type
Size Category
Test Procedure
Air conditioners, air cooled
(cooling mode)
<19 kW
All
Split systems
4.10 SCOPC 3.52
COPC
ARI 210/240
Single packaged
4.10 SCOPC 3.40
COPC
Through-the-wall air cooled
(cooling mode)
<9 kW
All
Split systems
3.52 SCOPC
Single packaged
3.52 SCOPC
Small-duct high velocity, air
cooled (cooling mode)
<9 kW
All
Split systems
2.93 SCOPC
Air conditioners, air cooled
(cooling mode)
≥19 kW and
<40 kW
Electric
resistance
(or none)
Split systems and
single package
3.31 COPC 3.46
ICOPC
ARI 340/360
All other
Split systems and
single package
3.25 COPC 3.40
ICOPC
≥40 kW and
<70 kW
Electric
resistance
(or none)
Split systems and
single package
3.32 COPC 3.46
ICOPC
All other
Split systems and
single package
3.25 COPC 3.40
ICOPC
≥70 kW
Electric
resistance
(or none)
Split systems and
single package
2.87 COPC 2.87
ICOPC
All other
Split systems and
single package
2.81 COPC 2.81
ICOPC
 
Search WWH ::