TABLE 9.1 (Continued)
Electrical Operated Unitary Air Conditioners and Condensing Units
Heating
Section
Type
Subcategory
or Rating
Conditions
Equipment
Type
Size
Category
Minimum
Efficiency
Test
Procedure
All other
Split systems
and single
package
4.04 COP
4.13 ICOP
ARI 340/360
≥40 kW
and
<70 kW
Electric
resistance
(or none)
Split systems
and single
package
4.10 COP
4.19 ICOP
ARI 340/360
All other
Split systems
and single
package
3.81 COP
4.13 ICOP
ARI 340/360
≥70 kW
Electric
resistance
(or none)
Split systems
and single
package
4.10 COP
4.10 ICOP
ARI 340/360
All other
Split systems
and single
package
3.81 COP
3.81 ICOP
ARI 340/360
Condensing
units, air
cooled
≥40 kW
[Not
applicable
match with
indoor
coil]
ARI 365
Condensing,
water or
evaporative
cooled
≥40 kW
[Not
applicable
match with
indoor coil]
ARI 365
9.3.2 Ventilation Controls for High-Occupancy Areas
Demand control ventilation (DCV) is required for densely occupied spaces . This
requirement supersedes the occupant density threshold in Section  4 of
EEECBC [6].
If CO 2 sensors are used as part of a DCV system, they shall be designed
and installed as defined in the following section.
CO 2 Sensors
Spaces with CO 2 sensors or air-sampling probes leading to a central CO 2
monitoring station shall have one sensor or probe for each 10,000 ft² (1000 m²)
of floor space and shall be located in the room between 3 ft and 6  ft (1  m
and 2  m) above the floor. CO 2 sensors must be accurate to ±50 ppm  at
1000 ppm. For all spaces with CO 2 sensors, target concentrations shall be cal-
culated for full and part load conditions (to include no less than 25%, 50%,
75% and 100%). Metabolic rate, occupancy, ceiling height and outdoor air CO 2
 