Environmental Engineering Reference
In-Depth Information
Water source (cooling mode)
<5 kW
All
30°C Entering water
4.10 COPC
ISO-13256-1
≥5 kW and
<19 kW
All
30°C Entering water
4.10 COPC
>19 kW and
<40 kW
All
30°C Entering water
4.10 COPC
Groundwater source (cooling
mode)
<40 kW
All
15°C Entering water
4.75 COPC
All
25°C Entering water
13.4 COPC
Air conditioners, air cooled
(heating mode)
<19 kW
All
Split systems
2.49 SCOPH
ARI 210/240
Single packaged
2.34 SCOPH
Through-the-wall air cooled
(heating mode)
<9 kW
All
Split systems
2.17 SCOPH
Single packaged
2.17 SCOPH
Small-duct high velocity,
air cooled (heating mode)
<19 kW
All
Split systems
1.99 SCOPH
Air cooled (heating mode)
≥19 kW and
<40 kW
(cooling capacity)
8°C DB/6 C WB
outdoor air
3.3 COPH
ARI 340/360
−8°C DB/−9 C WB
outdoor Air
2.2 COPH
≥40 kW (cooling
capacity)
8°C DB/6 C WB
outdoor air
3.2 COPH
−8°C DB/−9 C WB
outdoor air
2.0 COPH
Water source (heating mode)
<40 kW (cooling
capacity)
19°C Entering water
4.2 COPH
ISO-13256-1
Groundwater source (heating
mode)
<19 kW (cooling
capacity)
10°C Entering water
3.6 COPH
0°C Entering luid
3.1 COPH
 