TABLE 9.4 (Continued)
Electrically Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Packaged Vertical Air Conditioners, Single
Packaged Vertical Heat Pumps, Room Air Conditioners and Room Air Conditioner Heat Pumps - Minimum Eficiency Requirements
Subcategory or Rating
Condition
Minimum
Eficiency (SI)
Equipment Type
Size Category (Input)
Test Procedure
SPVHP (cooling mode)
<19 kW
35°C DB/23.9 C WB outdoor air
3.81 SCOPC
>19 kW and 40 kW Btu/h
35°C DB/23.9 C WB outdoor air
3.37 COPC
>40 kW and <70 kW
35°C DB/23.9 C WB outdoor air
3.37 COPC
SPVHP (heating mode)
<19 kW
8.3°C DB/6.1 C WB outdoor air
3.0 COPH
>19 kW and <40 kW Btu/h
8.3°C DB/6.1 C WB outdoor air
3.0 COPH
>40 kW and <70 kW
8.3°C DB/6.1 C WB outdoor air
2.9 COPH
Room air conditioners, with louvred
sides
<1.8 kW
3.14 SCOPC
ANSI/AHAM RAC-1
>1.8 kW and <2.3 kW
3.14 COPC
>2.3 kW and <4.1 kW
3.17 COPC
>4.1 kW and <5.9 kW
3.14 COPC
>5.9 kW
2.73 COPC
Room air conditioners, without louvred
sides
<2.3 kW
2.90 COPC
>2.3 kW and <5.9 kW
2.73 COPC
>5.9 kW
2.73 COPC
Room air conditioner heat pump with
louvred sides
<5.9 kW
2.90 COPC
>5.9 kW
2.73 COPC
Room air conditioner heat pump
without louvred sides
<4.1 kW
2.73 COPC
>4.1 kW
2.58 COPC
Room air conditioner, casement only
All capacities
2.81 COPC
Room air conditioner, casement-slider
All capacities
3.05 COPC
 