TABLE 9.4
Electrically Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Packaged Vertical Air Conditioners, Single
Packaged Vertical Heat Pumps, Room Air Conditioners and Room Air Conditioner Heat Pumps - Minimum Eficiency Requirements
Subcategory or Rating
Condition
Minimum
Eficiency (SI)
Equipment Type
Size Category (Input)
Test Procedure
PTAC (cooling mode) new construction
<2.0 kW
35°C DB outdoor air
3.49 COPC
ARI 310/380
≥2.0 kW and <2.9 kW
35°C DB outdoor air
3.31 COPC
≥2.9 kW and <3.8 kW
35°C DB outdoor air
3.14 COPC
≥3.8 kW
35°C DB outdoor air
3.48 COPC
PTAC (cooling mode) replacement
<2.0 kW
35°C DB outdoor air
3.49 COPC
ARI 310/380
≥2.0 kW and <2.9 kW
35°C DB outdoor air
3.31 COPC
≥2.9 kW and <3.8 kW
35°C DB outdoor air
3.14 COPC
≥3.8 kW
35°C DB outdoor air
3.48 COPC
PTHP (cooling mode) new construction
<2.0 kW
35°C DB outdoor air
3.48 COPC
ARI 310/380
≥2.0 kW and <2.9 kW
35°C DB outdoor air
3.48 COPC
≥2.9 kW and <3.8 kW
35°C DB outdoor air
3.48 COPC
≥3.8 kW
35°C DB outdoor air
3.48 COPC
PTHP (heating mode) new construction
All capacities
35°C DB outdoor air
2.8 COPH
ARI 310/380
PTHP (cooling mode) replacement
<2.0 kW
35°C DB outdoor air
3.43 COPC
ARI 310/380
≥2.0 kW and <2.9 kW
35°C DB outdoor air
3.25 COPC
≥2.9 kW and <3.8 kW
35°C DB outdoor air
3.08 COPC
≥3.8 kW
35°C DB outdoor air
2.73 COPC
PTHP (heating mode) replacement
All capacities
35°C DB outdoor air
2.8 COPH
ARI 310/380
SPVAC (cooling mode)
<19 kW
35°C DB/23.9 C WB outdoor air
3.81 SCOPC
ARI 390
>19 kW and <40 kW Btu/h
35°C DB/23.9 C WB outdoor air
3.37 COPC
>40 kW and <70 kW
35°C DB/23.9 C WB outdoor air
3.37 COPC
Continued
 