Fig. 6.1 Downstand beam system requiring strengthening
Fig. 6.2 Section through downstand beam, (section A-A)
p rare g 1 ; k g 2 ; k q k
30
5
50
85 kN
=
m
In order to determine the prestrain condition during strengthening, which according to
DAfStb guideline [1, 2] part 1 section 5.1.1 (RV 19) must be considered for a quasi-
permanent load combination, we get the following for load case 2:
X
X
i 1 ψ 2 ; i ? Q k ; i
G k ; j P
j 1
p perm g 1 ; k
30 kN
=
m
Loads on the system in kN/m 2 for the various load cases.
Table 6.1
Load case
1
2
3
g 1,k (dead load)
30.0
30.0
30.0
g 2,k (
(fitting-out load)
5.0
5.0
q k (imposed load, category B)
25.0
50.0