Environmental Engineering Reference
In-Depth Information
Table 4.2 Measured energy delivered by the five vertical ground heat exchangers to the SIC building
in Freiburg, Germany
Hours
Hours
Cooling
Heating
COP
COP
cooling
cooling
Hours
Year
/ kWh
/ kWh
cool
heat
seminar
floor
heating
2005
2759
2846
20.1
12.8
233
2289
856
2006
4873
246
13.5
5.2
327
2911
289
Due to the significantly longer operating hours of both the ventilation system of
the seminar room and the floor cooling system in 2006, the cooling energy delivered
by the geothermal heat exchangers nearly doubled from 2.76 to 4.87 MWh. This
corresponds to 7-12 kWh per metre of heat exchanger and summer. The low COP
for heating in 2006 is due to the fact that the geothermal system was often operated
at a low temperature difference between the ambient air and ground heat exchanger.
Table 4.2 summarizes the measured results.
4.1.4 Modelling of Geothermal Heat Exchangers
Numerical heat transfer models for geothermal heat exchangers were developed and
implemented in the simulation environment INSEL. They are all based on the heat
conduction equation with explicit finite difference solutions. The simplest vertical
heat exchanger model uses a rectangular discretization geometry. Horizontally, nine
zones have been defined and, vertically, 30 elements are calculated for each time step
with only one-dimensional heat transfer considered (see Figure 4.23). To determine
Near soil
Filling material
Far soil
Brine inlet
Brine outlet
1
2
3
4
5
6
7
8
9
Undisturbed soil
Figure 4.23 Geometry of horizontal discretization of the two-dimensional model for a vertical earth
heat exchanger
 
Search WWH ::




Custom Search