For f c = 4000 psi:
P u
512
96.7 +
(
)
h
=
4.15c
A f +
2in.
=
4.15 4.25
2
=
40.6
+
2
=
42.6in.
Bearing on column:
Allowable bearing load = 0.85
φ
f c A g ,
φ
= 0.55
ACI 318, Section 22.5.5
= 0.85
0.55
4
16 2 = 479 kips < P u 501 kips
The excess compression must be transferred to the footing by reinforcement consisting of extended column
bars or dowels (calculations not show).
Figure 7-11 illustrates the footing for this case.
4-#8 column bars
4-#6 dowels x 4'-0"
9'-6" square
Figure 7-11 Plain Concrete Footing for Interior Column of Building No. 2 (Non-sway Frame)
References
7.1 Notes on ACI 318-08 , Chapter 7, Design for Flexure, 10th Edition, EB708, Portland Cement Association,
Skokie, Illinois, 2008.
7.2 Building Code Requirements for Structural Concrete ACI 318-11 and Commentary , American Concrete
Institute, Farmington Hills, Michigan, 2011.
 