Try 16 in. pan forms * + 3 1 / 2 -in. slab
h = 19.5 in. > 17.8 in. O.K.
slab thickness = 3.5 in. > 3.2 in.
O.K.
(4)
Determine width of joist rib
(a) Code minimum (ACI 8.13.2):
b w > 16/3.5 = 4.6 in. > 4.0 in.
(b) For flexural strength:
20M u
d 2
20(57.5)
18.25 2
b w =
=
=
3.45 in.
where d = 19.5 - 1.25 = 18.25 in. = 1.52 ft
Check for fire resistance: from Table 10-4 for restrained members, the required cover for a fire
resistance rating of 1 hr = 3 / 4 -in. for joists.
(c) For shear strength
V u @ distance d from support face = 12.0 - 0.76(1.52) = 10.84 kips
φ
V c = 1.1(0.095b w d) = 0.11b w d**
b w
= 10.84/(0.11 x 18.25) = 5.40 in.
Use 6 in. wide joists (see Table 9-3 and Fig. 3-17).
(5)
Determine Flexural Reinforcement
(a)
Top bars at spandrel beams:
M u
24.0
4(18.25) =
A s =
4d =
0.33 in. 2
Distribute bars uniformly in top slab:
A s = 0.33/3 = 0.11 in. 2 /ft
*
See Table 9-3 for standard form dimensions for one-way joists.
** For standard joist ribs conforming to ACI 8.13 a 10% greater shear strength fVc is allowed. Also, minimum shear
reinforcement is not required (see ACI 11.4.6).
 