Figure G5-9
Partial load cases
for roof purlins in
Example 5-2.
Solution
As before, C e is 1.0, I s is 1.2, and p g is 20 lb/ft 2 , but now C t is 1.0 and the
roof slope factor from Figure 7-2(a) is as follows:
. oo
14
5
C s
=
10
086
.
=
o
65
The fl at roof snow load becomes
16.8 lb/ft 2
p f
=
0.7 C e C t I s p g =
0.7(1.0)(1.0)(1.2)(20)
=
(round to 17 lb/ft 2 )
The balanced snow load is
0.86 (17 lb/ft 2 )
14.6 lb/ft 2 (round to 15 lb/ft 2 )
p s =
C s p f =
=
For 5 ft purlin spacing, the full- and half-balanced loads are
balanced
=
15 lb/ft 2
×
5.0 ft
=
75 lb/ft
half-balanced = ½(75 lb/ft) = 37.5 lb/ft (round to 38 lb/ft)