TABLE 9.12
Minimum Duct Insulation R-Values, Combined Heating and Cooling Supply Ducts and Return Ducts
Duct Location
Climate
Zone
Ventilated
Attic
Unvented Attic above
Insulated Ceiling
Unvented Attic with
Roof Insulation
Unconditioned
Space
Indirectly
Conditioned Space
Exterior
Buried
Supply Ducts
1
R-1.41
R-1.41
R-1.76
R-1.06
R-1.06
None
R-1.06
2
R-1.41
R-1.41
R-1.41
R-1.06
R-1.41
None
R-1.06
3
R-1.41
R-1.41
R-1.41
R-1.06
R-1.41
None
R-1.06
4
R-1.41
R-1.41
R-1.41
R-1.06
R-1.41
None
R-1.06
5
R-1.41
R-1.41
R-1.41
R-0.62
R-1.41
None
R-1.06
6
R-1.76
R-1.41
R-1.41
R-0.62
R-1.41
None
R-1.06
7
R-1.76
R-1.41
R-1.41
R-0.62
R-1.41
None
R-1.06
8
R-1.76
R-1.94
R-1.94
R-0.62
R-1.41
None
R-1.41
Return Ducts
1-8
R-1.06
R-1.06
R-1.06
None
None
None
None
Source: EEECBC EGYPTIAN Energy Eficiency Code, HBRC, 2012.
Note: Insulation R-values, measured in m 2 k/kW, are for the insulation as installed and do not include ilm resistance. The required minimum
thicknesses do not consider water vapour transmission and possible surface condensation. Where exterior walls are used as plenum walls,
wall insulation shall be as required by the most restrictive condition of 6.4.4 2 or Section 5. Insulation resistance measured on a horizontal
plane in accordance with ASTM C518 at a mean temperature of 23.8°C at the installed thickness. Includes crawl spaces, both ventilated and
non-ventilated. Includes return air plenums with or without exposed roofs above.
 