Environmental Engineering Reference
In-Depth Information
TABLE 9.1
Electrical Operated Unitary Air Conditioners and Condensing Units
Heating
Section
Type
Subcategory
or Rating
Conditions
Equipment
Type
Size
Category
Minimum
Efficiency
Test
Procedure
Air
conditioners,
air cooled
<19 kW
All
Split systems
4.10 SCOP
3.52 COP
ARI 210/240
Single
packaged
4.10 SCOP
3.52 COP
ARI 210/240
Through-the-
wall air
cooled
<9 kW
All
Split systems
3.52 SCOP
ARI 210/240
Single
packaged
3.52 SCOP
ARI 210/240
Small-duct
high-velocity,
air cooled
<19 kW
All
Split systems
2.93 SCOP
ARI 210/240
Air
conditioners,
air cooled
≥19 kW
and
<40 kW
Electric
resistance
(or none)
Split systems
and single
package
3.37 COP
3.52 ICOP
ARI 340/360
All other
Split systems
and single
package
3.31 COP
3.46 ICOP
ARI 340/360
≥40 kW
and
<70 kW
Electric
resistance
(or none)
Split systems
and single
package
3.37 COP
3.52 ICOP
ARI 340/360
All other
Split systems
and single
package
3.31 COP
3.46 ICOP
ARI 340/360
≥70 kW
and
<223 kW
Electric
resistance
(or none)
Split systems
and single
package
2.93 COP
3.08 ICOP
ARI 340/360
All other
Split systems
and single
package
2.87 COP
3.02 ICOP
ARI 340/360
≥223 kW
Electric
resistance
(or none)
Split systems
and single
package
2.84 COP
2.99 ICOP
ARI 340/360
All other
Split systems
and single
package
2.78 COP
2.93 ICOP
ARI 340/360
Air
conditioners,
water and
evaporative
cooled
<19 kW
All
Split systems
and single
package
4.10 COP
4.19 ICOP
ARI 210/240
≥19 kW
and
<40 kW
Electric
resistance
(or none)
Split systems
and single
package
4.10 COP
4.19 ICOP
ARI 340/360
 