Ultimate bearing capacity, Q u   =  653.5  ×  L  ×  B   =  15 174 kN
Q
15174
1
u
Bearing resistance R
,
=
=
=
15 174
kN
d
γ
Rv
R
F
15174
2850 1
d
Over-design factor
,
Γ =
=
=
5 32
.
.
d
Since Γ   >  1, the GEO limit state requirement is satisfied.
Example 9.7:  Bearing resistance - undrained & drained
It is proposed to place a 2 m  ×  2 m square footing at a depth of 1.5 m in a glacial clay soil as shown
in Figure 9.11. The 0.5 m thick footing is to support a 0.4 m  ×  0.4 m centrally located square column
which will carry a vertical characteristic permanent load of 800 kN and a vertical characteristic
transient load of 350 kN. Take the unit weight of reinforced concrete, γ concrete as 25 kN/m 3 .
The soil has the following properties:
undrained shear strength, c u   =  200 kPa
effective cohesion, c   =  0 kPa
angle of shearing resistance, φ   =  28°
weight density, γ   =  20 kN/m 3
The ground water table is coincident with the base of the foundation.
Check compliance of the bearing resistance limit state using Design Approach 1 for:
ii. the short-term state;
ii. the long-term state;
Solution:
(i) Representative actions:
Self weight of concrete:
W
= × × +
(
B L t B
× × −
L
(
z
t
)
γ
concrete
col
col
concrete
=
[(
2 0 2 0 0 5 +
.
×
.
×
.
)
(
0 4 0 4 1 0
.
×
.
×
.
)]
×
25
=
54 0 kN
.
G k = 800 kN
Q k = 350 kN
0.4 m × 0.4 m
1.5 m
0.50 m
2.0 m
Fig. 9.11 Example 9.7.
 