Environmental Engineering Reference
In-Depth Information
Table 3-10 Approximate feed rate settings for 100 mg/L chlorine dosage
at various flow rates (liquid chlorine feed)
US Units
SI Units
Flow Rate
gpm
Feed Rate Setting
lb/day
Flow Rate
L/sec
Feed Rate Setting
g/hr
10
12
0.5
180
20
24
1 .0
360
30
36
1.5
540
40
48
2 .0
720
50
60
2.5
900
60
72
3 .0
1,080
70
84
3.5
1,260
80
96
4 .0
1,440
90
108
4.5
1,620
100
120
5 .0
1,800
Table
Tamer
This table shows the approximate chlorinator feed rate
settings for various fill rates to achieve 100 mg/L dosage.
To get the setting for other dosages, just multiply the setting
for 100 mg/L by the ratio: other dosage/100 mg/L.
Example: The pipeline fill rate is 30 gpm but the desired
dosage is 25 mg/L. For a 30 gpm fill rate the chlorinator
feed setting from the table is 36 lb/day. Multiply this setting
times the ratio 25/100 = 9 lb/day.
Use the chlorination chemical amount calculation checklist on
page 28 to ensure that you have all of the items needed to make
the calculation.
The pipeline diameter and length are used to calculate the
volume of the pipeline from Table 3-6.
The number of valves, hydrants, and other appurtenances
determine the number of tablets needed for disinfection of
these items. Usually one tablet for each is adequate.