Environmental Engineering Reference
In-Depth Information
gal/min
×
25 mg/L
×
3.785 L/gal ÷ %
×
0.01
×
1,000 mg/g
×
1 mL/g = mL/min
(c3-3)
Sodium
hypochlorite
solution feed
rate (mL/min)
Strength of
sodium
hypochlorite
feed solution (%)
Water fill
rate (gpm)
total
=9.46
×
÷
(c3-4)
Sodium
hypochlorite
solution feed
rate (gal/hr)
Strength of
sodium
hypochlorite
feed solution (%)
Water fill
rate (gpm)
total
=0.15
×
÷
L/sec
×
25 mg/L
×
1,000 mL/L
×
60 sec/min
×
0.001 L/mg
×
0.01 ÷ % = mL/min
(c3-5)
Sodium
hypochlorite
solution feed
rate (mL/min)
Strength of
sodium
hypochlorite
feed solution (%)
Water fill
rate (L/sec)
total
=
150
×
÷
Tank Volume Calculators
Rectangular or Square Tanks
(c5-1)
Maximum
depth of
water, in ft
Volume,
in gal
Length,
in ft
Width,
in ft
7.48 gal/ft 3
×
=
×
×
(c5-2)
Maximum
depth of
water, in m
Length,
in m
Width,
in m
Volume,
in m 3
×
×
=
Search WWH ::




Custom Search