Environmental Engineering Reference
In-Depth Information
The withdrawal rate for a 20% slug (c8-4) = 39,250 L
×
180 min (3 hr) = 218 L/min.
Convert to L/sec: 218 L/min
60 sec/min = 3.6 L/sec
×
1% hypochlorite feed rate from Table 8-5 is 2,400 mL/min
for a fill rate of 4 L/sec. This will result in a chlorine dosage
slightly higher than 100 mg/L.