Fig. 7.70 Solar heat gain and daylight illuminance of thermal zones
Table 7.17 Space cooling energy of different design and operation
scenarios
Exterior
Reflector
Nighttime
Ventilation
Space Cooling Energy Consumption per
Meter Façade Width (kWh/m)
No
no
7.10
Yes
no
7.20
Yes
10 ACH
4.13
Yes
30 ACH
3.82
Nighttime building free cooling with outdoor cool air is adopted to reduce
the space cooling load. Whenever the room temperature is less than 3 °C
lower than the daytime room temperature setpoint and exterior air
temperature is lower than room air temperature, free cooling is activated.
Increasing the ventilation rate from 10 to 30 ACH results in a marginal
reduction(4.3%)incoolingenergyconsumption.Thereisalsonosignificant
 
 