Fig. 7.63
Comparison of measured (M) and simulated (S) thermal
performance for Jan. 16. (a) North thermal zone; (b) south zone and the
simulated solar heat gain
Based on the measured 24 h slab and room temperature profiles in
Figure
7.63
and weather conditions in
Figure 7.54
, 0.90 kWh/m façade width of
heating is required for the south zone, 0.21 kWh/m for the interior zone,
and 2.75 kWh/m for the north zone. The energy for warming up the exterior