Civil Engineering Reference
In-Depth Information
4.4.2 Testing Procedure
The beams were tested with simple supports and were subjected to two point loads.
The distance between supports was 5.00 m and the shear span/depth ratio (a/d) was
3.0 in all cases, except for beam HF400h/6, with a/d = 2.8.
The two loads were applied to the beams by one 2,500 kN hydraulic jack applied
at a rate of 0.5
2.0 kN/s. To monitor the behavior of the beams, the applied loads
and vertical deflections were measured using a load cell and three displacement
transducers placed on the middle span at the center of each shear span. All the
variables were continuously registered by the data acquisition system. Photography
and video cameras were also utilized in both the shear span zones on both sides of
the beams. A synchronized recording system allowed us to assign each photogram
to the corresponding load. The maximum shear crack opening versus load curve
was obtained from a photo analysis. Figure 4.5 shows the test set-up.
-
4.4.3 Results
As expected, all the beams suffered shear failure and presented diagonal cracks
accompanied by minor
exural cracks. Table 4.4 shows the maximum load obtained
for each beam. Greater shear capacity was obtained when stirrups and
fl
ber acted
simultaneously (Beams HF600TR/1 and HF600TR/2), reaching a value of 18.5 %
higher than that of the beam with traditional stirrups only (Beam H600TR/3).
No signi
cant difference was found between the two beams with both stirrups
Fig. 4.5 Beam during shear test
Search WWH ::




Custom Search