Calculate factored shear force—V u
The factored shear force V u at the critical section is
V u =105.72×25/2-105.72×3.75=925.0 kips.
Nominal shear strength V n and resisting capacity V c
hence V c =922120 lb controls
Shear reinforcement
Assume No. 4 bars placed both horizontally and vertically on both faces of
the beam.
A v = A vh =2×0.20=0.40 in 2
f
V s = V u -
f
V c
V s =( V u /
f
)- V c =(925 000/0.85)-922 120=166 115 lb
Assume that s =18 in in centre to centre and s 2 =10.5 in centre to centre,
hence
=333642 lb>116 115 lb ? OK
The maximum permissible spacing of vertical bar: s = d /5 or 18.0 in which
ever is smaller; s =162/5=32.4 in. Hence 18.0 in controls, use s =18.0 in.
The maximum permissible spacing of horizontal bar: s 2 = d /3 or 18.0 in
whichever is smaller; s 2 =162/3=54.0in. Hence 10.5 in controls use
s 2 =10.5 in.
Check for minimum steel:
Minimum A v =0.0015 bs =0.0015×15×18=0.40 in 2 OK
Minimum A vh =0.0025 bs 2 =0.0025×15×10.5=0.393 in 2
OK
Figure 5.11 shows the reinforcement details.