F i g u r e 10.6 Force transfer methodology.
Determine the overturning force (see Fig. 10.7): Most of the examples in other
publications ignore the location of the centerline of the hold-down anchor and center
of bearing, when determining the moment-resisting arm. This is usually so because
the eccentricity of the hold-down with respect to the outer edge of the panel is
difficult to address, when analyzing a wall with the FTO method. In this example,
embedded tie strap anchors are installed at each end of the wall, as shown in the
figure, to eliminate the eccentricity problem.
200 14 5
2
(. )
2
1
14 5
T left =
4500 9
()
=
1343 1
. btension
.
200 14 5
2
(. )
2
1
14 5
C right =
4500 9
()
+
=
4243
.1lbcompression
.
 