yield strength of the flanges, and where
b f t f
t w h w
f yf
f yw
c = a
0.25 + 1.6
.
(4.88)
Worked examples of checking the shear capacity of a slender web are given in
Sections 4.9.5 and 4.9.6.
4.7.5.3 Transverse stiffeners
Provisions are made in EC3 for a minimum value for the second moment of area
I st of intermediate transverse stiffeners.These must be stiff enough to ensure that
the elastic buckling stress τ cr of a panel can be reached, and strong enough to
transmit the tension field stiffener force. The stiffness requirement of EC3 is that
the second moment of area of a transverse stiffener must satisfy
I st 0.75 h w t w ,
(4.89)
when a / h w > 2, in which h w is the depth of the web, and
I st 1.5 h w t w / a 2
(4.90)
when a / h w 2.TheselimitsareshowninFigure4.29,andareclosetothoseof
equations 4.27 and 4.26.
The strength requirement of EC3 for transverse stiffeners is that they should
be designed as compression members of length h w with an initial imperfection
2
equation 4.27
1
equation 4.89
equation 4.26
equation 4.90
0 0
1
2
3
Value of a/d
Figure 4.29 Stiffness requirements for web stiffeners.