Environmental Engineering Reference
In-Depth Information
Figure 15.3.3
SHAC using absorption chiller for displacement ventilation.
Table 15.3.4
Summary of cooling and energy performances of SHAC and conventional systems for
DV and MV.
Year-round
Year-round
Type of
averaged
Year-round
total E
p
per
Energy saving
ventilation
T
z
(
◦
C)/
Year-round
averaged
AC area
vs.WCVCC
(kWh/m
2
)
Type of system collectors
RH
z
(%)
averaged SF
COP
ch
/COP
dc
using MV
SHAC-Ab
DV
25.1/59.1
0.905
0.809/0.845
192
49.5%
MV
24.9/58.3
0.804
0.779/0.904
246
35.3%
SHAC-Ad
DV
25.0/59.3
0.741
0.475/0.880
310
18.3%
MV
24.9/58.4
0.590
0.460/0.919
445
−
17.2%
WCVCC
DV
24.4/70.3 NA
3.556/NA
273
NA
WCVCC
MV
24.8/58.9 NA
3.195/NA
380
NA
Remarks: NA means not applicable.
and conventional AC systems, as shown by Fong et al. (2011b), are consolidated in
Table 15.3.4.
Table 15.3.4 summarizes the year-round performances of the different systems. All
of them can maintain satisfactory indoor conditions of averaged T
z
and RH
z
, except
the WCVCC for DV, which has a RH
z
of 70.3% due to the relatively high supply
air humidity ratio. When compared to the conventional WCVCC for MV, the SHAC
systems are technically feasible, with a primary energy saving of 49.5% for SHAC-Ab
and 18.3% for SHAC-Ad. In the same ventilation strategy the SHAC-Ab has a primary
energy saving of 29.7% against the conventional AC system for DV, and 35.3% against
that for MV. Even the SHAC-Ab for MV has an energy saving of 9.9% against the
conventional system for DV. This really demonstrates the effectiveness of the hybrid
design of solar air-conditioning systems using absorption chillers.
When compared to MV counterparts, the adoption of DV can reduce total primary
energy consumption from 246 kW/m
2
to 192 kW/m
2
(a 21.9% drop) in SHAC-Ab; and
Search WWH ::
Custom Search