Environmental Engineering Reference
In-Depth Information
Figure 15.3.1 SHAC using adsorption chiller for radiant cooling with chilled panels or passive chilled
beams.
Figure 15.3.2 SHAC using adsorption chiller for radiant cooling with active chilled beams (New
abbreviation: RAF: return air fan).
Table 15.3.3 Summary of cooling and energy performances of SHAC systems with radiant cooling.
Year-round
Year-round
Energy saving
averaged
Year-round
total E p per
vs. ACVCC/
Type of chilled
T z ( C)/
Year-round
averaged
AC area
WCVCC
(kWh/m 2 )
Type of system collectors
RH z (%)
averaged SF
COP ch
inTable 1
SHAC-Ab
Chilled panels
29.0/42.8
0.782
0.840
209
46.2%/45.0%
Passive chilled
beams
25.4/52.2
0.882
0.830
137
64.7%/63.9%
Active chilled
beams
25.1/52.2
0.828
0.823
191
50.8%/49.6%
SHAC-Ad
Chilled panels
29.0/43
0.614
0.564
365
6.1%/3.9%
Passive chilled
beams
25.4/53
0.754
0.558
228
41.2%/39.9%
Active chilled
beams
25.0/53
0.689
0.548
311
20.0%/18.1%
 
Search WWH ::