Environmental Engineering Reference
In-Depth Information
giving
s
2
C
ð
P
C
dt
V
DC
¼
ð
3
:
41
Þ
By substituting
P
C
in (3.37) in (3.41), the DC-link voltage
V
DC
can be expressed in
terms of the generator output power,
P
S
gen
, and the power transmitted to the grid,
P
S
grid
,as
s
2
C
ð
V
DC
¼
ð
P
S
gen
P
S
grid
Þ
dt
ð
3
:
42
Þ
Equation (3.42) calculates the actual value of
V
DC
. The reference value of the
active power,
P
ref
S
grid
, to be transmitted to the grid is calculated by comparing the
actual DC-link voltage,
V
DC
, with the desired DC-link voltage reference,
V
DC
ref
.
The error between these two signals is processed by a PI controller, whose output
provides the reference active power
P
ref
S
grid
, as shown in Figure 3.29. It should be
noted that in a physical implementation the actual value of the DC-link voltage,
V
DC
, is obtained from measurements via a transducer.
To implement the load angle controller the reference value of the reactive
power,
Q
ref
S
grid
, may be set to zero for unity power factor operation. Hence, the
magnitude,
V
S
, and angle,
d
, required at the terminals of the grid-side converter are
calculated using (3.29) and (3.30) as
P
ref
S
grid
X
grid
V
S
V
R
d ¼
ð
3
:
43
Þ
Q
ref
S
grid
X
grid
V
S
S
grid
¼
0
ð
3
:
44
Þ
Q
ref
V
S
¼
V
R
þ
;
Figure 3.30 illustrates the implementation of the load angle control scheme for the
grid-side converter with unity power factor. If the reactive power exchange with the
network is not zero it should be noted that (3.44) is transcendental.
Integrator
ref
S
grid
V
DC
P
P
S
gen
PI
controller
2
C
∫
-
+
-
+
V
DC
ref
P
S
grid
Calculation of active power reference, P
ref
S
grid
Figure 3.29
(suitable for simulation
purposes)
Search WWH ::
Custom Search