Environmental Engineering Reference
In-Depth Information
giving
s
2
C
ð P C dt
V DC ¼
ð 3 : 41 Þ
By substituting P C in (3.37) in (3.41), the DC-link voltage V DC can be expressed in
terms of the generator output power, P S gen , and the power transmitted to the grid,
P S grid ,as
s
2
C
ð
V DC ¼
ð P S gen P S grid Þ dt
ð 3 : 42 Þ
Equation (3.42) calculates the actual value of V DC . The reference value of the
active power, P ref
S grid , to be transmitted to the grid is calculated by comparing the
actual DC-link voltage, V DC , with the desired DC-link voltage reference, V DC ref .
The error between these two signals is processed by a PI controller, whose output
provides the reference active power P ref
S grid , as shown in Figure 3.29. It should be
noted that in a physical implementation the actual value of the DC-link voltage,
V DC , is obtained from measurements via a transducer.
To implement the load angle controller the reference value of the reactive
power, Q ref
S grid , may be set to zero for unity power factor operation. Hence, the
magnitude, V S , and angle, d , required at the terminals of the grid-side converter are
calculated using (3.29) and (3.30) as
P ref
S grid X grid
V S V R
d ¼
ð 3 : 43 Þ
Q ref
S grid X grid
V S
S grid ¼ 0
ð 3 : 44 Þ
Q ref
V S ¼ V R þ
;
Figure 3.30 illustrates the implementation of the load angle control scheme for the
grid-side converter with unity power factor. If the reactive power exchange with the
network is not zero it should be noted that (3.44) is transcendental.
Integrator
ref
S grid
V DC
P
P S gen
PI
controller
2
C
-
+
-
+
V DC ref
P S grid
Calculation of active power reference, P ref
S grid
Figure 3.29
(suitable for simulation
purposes)
Search WWH ::




Custom Search