Controller-1
Controller-2
Figure 3.25
Wide-range synchronous generator wind turbine with a PWM-VSC
generator-side converter
V S d
V R ∠0
j X
Receiving
source
Sending
source
I
S S = P S + j Q S
(a) Equivalent circuit diagram
V S
δ =
load angle
φ = power factor angle
j X I
δ
φ
V R
I
(b) Phasor diagram
Figure 3.26
Power transfer between two sources (Kundur, 1994)
Tan and Islam, 2004). The grid-side converter is normally controlled using load
angle control techniques. In this section we explain the implementation of the load
angle control scheme assuming a permanent magnet generator.
3.6.2.4 Load angle control
The load angle control technique can be explained by analysing the transfer of
active and reactive power between two sources connected by an inductive reac-
tance as shown in Figure 3.26a. The active power, P s , and reactive power, Q s ,