Environmental Engineering Reference
In-Depth Information
characteristic. (This is an absolute minimum and if the
WFPS
can offer a larger response it should do so.)
2.
Secondary Response
capability of the
WFPS
(avail-
able by 30 seconds and sustained): 100% of the expec-
ted
MW Output
value based upon droop characteristic.
(b)
This
Fast Acting
proportional governor should be equipped
with controls which allow the droop to be set independently
in the range 2-20% above and below 50.0 Hz. A
Governor
Dead Band
within which no control will be exercised must
be capable of being set with a lower limit between 49.0 and
50.0 Hz in steps of 0.05 Hz and an upper limit between
50.0 and 51.0 Hz in steps of 0.05 Hz. Whilst responding to
Frequency
excursions on the
System
the change in
Output
of the
Controllable WFPS
shall be at the
Frequency
Response
Ramp Rate
. In addition a high
Frequency
trip
facility must be provided capable of being set in the range
51.0-52.0 Hz in steps of 0.1 Hz. Unless the
Developer/
Generator
is notified otherwise by the
TSO
,the
Governor
Droop
,
Governor Dead Band
and high
Frequency
trip
settings shall be as specified by the
TSO
from time to time
in the
WFPS Settings Schedule
published on the website
(or such other place or by such other means as may be
notified to the
Developer
/
Generator
from time to time).
Where a
Controllable WFPS
becomes isolated from the
rest of the
Transmission System
the
Controllable WFPS
must immediately detect the condition and shut itself down.
(c)
Under certain
System
conditions the
TSO
may require a
Controllable WFPS
to operate below its maximum instan-
taneous
Output
on a droop setting to be set in the range
2-20%. In this mode of operation the
Controllable WFPS
will be providing some of the
System
reserve. The
Con-
trollable WFPS
controller must be capable of being set to
operate in a constrained manner within the range of at least
50-100% of maximum instantaneous
Output
. This mode is
known as
Frequency Sensitive Mode
.
CC.S2.5.3
(a)
Each
Controllable WFPS
must be fitted with a
Fast Acting
control system capable of being switched to control the
Controllable WFPS
voltage,
Power Factor
or the
Reactive
Power
output at the
Connection Point
. These control modes
must maintain the voltage at the
Connection Point
within a
voltage band as specified within the
Connection Agreement
or other agreement for the particular site, and in any case
Search WWH ::
Custom Search