Environmental Engineering Reference
In-Depth Information
It shall be possible to vary the Normal Wind Following
Ramp Rate
and the
Active Power
Control
Ramp Rate
each
independently over a range between 1 and 100% of
Regis-
tered Capacity
per minute. Unless notified otherwise by the
TSO
,the
Developer
/
Generator
will initially set the con-
troller to the setting as specified by the
TSO
from time to time
in the
WFPS Settings Schedule
published on the website (or
such other place or by such other means as may be notified to
the
Developer
/
Generator
from time to time). The
Ramp
Rate
is the average rate of change in
Output
measured over
any10minuteperiod.The
Ramp Rate
averaged over 1 minute
should not exceed three times the average
Ramp Rate
over
10 minutes. The
Generator
shall alter settings in line with
changes to the
Settings Schedule
from time to time.
(b)
A
Controllable WFPS
shall have a ramp
Frequency
con-
troller, which on
Start-Up
and during normal operation of
any
Controllable WFPS
shall only allow an increase in
Output
when the
System Frequency
is below a set value.
This set value in the ramp
Frequency
controller should be
capable of being set in the range 50.0-51.5 Hz in steps of
0.1 Hz. Unless notified otherwise by the
TSO
,the
Developer
/
Generator
will initially set the controller to the setting as
specified by the
TSO
from time to time in the
WFPS Settings
Schedule
published on the website (or such other place or by
such other means as may be notified to the
Generator
from
time to time) and the
Generator
shall alter settings in line
with changes to the
Settings Schedule
from time to time.
(c)
During operation the
TSO
may send to the
Generator
a
positive ramp blocking signal if the
System
would otherwise
be at risk from excess
Frequency
movements. This signal is
designed to restrain
WFPSs
from ramping above the pre-
vious 10 minute average level at the time of receiving the
signal. The
WFPS
may continue to supply
Output
up to this
level until the signal is removed. The
TSO
will remove the
ramp blocking signal as soon as stable conditions on the
System
are restored, as determined by the
TSO
.
(d)
Unless the
Controllable WFPS
has a continually manned
control point, the
TSO
shall send a SCADA signal indicat-
ing that a process of increasing/decreasing
Output
is to be
initiated and the time interval over which the increase/
decrease of
Output
is to be achieved. A
Controllable
WFPS
receiving such a signal shall send a SCADA signal in
response confirming that it has received the SCADA signal
from the
TSO
. The rate of increase/decrease in
Output
of
the
Controllable WFPS
shall target the
Active Power
Search WWH ::
Custom Search