Environmental Engineering Reference
In-Depth Information
V pu
Transient
rating
1.0
Transient
rating
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
I C max
I L max
Figure A.7
STATCOM operating chart
the output voltage wave. The advantage of this device is that it can maintain con-
stant reactive power output down to about 0.2 pu system voltage, after which it falls
off proportionally to 0 at zero voltage (see Figure A.7). It has transient capability in
both the capacitive and inductive quadrants. Being based on voltage source con-
verter technology, the device can also act as an active harmonic filter.