quantity of objects. These settings will calculate the first four dryers at
100 percent, the next dryer at 85 percent, the next at 75 percent, and so
on.
Figure14.8
Incremental demand factor settings using the By Quantity
method
Figure 14.9
Total demand factor settings using the By Quantity
method
By Load
You use the By Load method to assign a demand factor to
different ranges of loads. You can assign different factors to ranges of
loads or the same factor to the total load connected to a panel.
Figure
14.10
shows the settings using this method incrementally for each range
defined. These settings will calculate the first 10,000 VA at 100 percent
and anything greater at 50 percent. The option to calculate the total at
one percentage would be used if you wanted to set the demand factor
for a total load range. For example, you could set the factor at 100