Environmental Engineering Reference
In-Depth Information
Type1
Type 2
Plant
feeders
Plant
feeders
Generator
Generator
PF control
capacitors
PF control
capacitors
ac
to
dc
Slip power
as heat loss
Type3
Type 4
Plant
feeders
Plant
feeders
ac
to
dc
dc
to
ac
Generator
Generator
ac
to
dc
dc
to
ac
Full power
Partial power
FIGURE 7.12 Four types of dynamic models, wind turbine connection to the grid.
however, the wind speeds are so variable it is improbable for self-excitation to last very long.
Fluctuations in voltage and frequency need to be kept within ranges acceptable to the utility at the
point of connection to the utility grid (Figure 7.13).
The faults on the utility grid will also cause a reaction from the wind turbines. A wind farm
was monitored for 1 year [11], and there were 215 faults. At the monitoring node the voltage drop
and spike in current describe the fault ( Figure 7.14 ). The fault events mostly occurred far from the
wind farm, and most were cleared within ten cycles. Therefore, voltage ride-through capability of
the wind turbines is important. For the doubly fed induction generator, the rotor currents increase
very rapidly and should be disconnected from the grid within milliseconds to protect the con-
verter. When constant-rpm wind turbines come back online they need a lot of reactive power, which
impedes the voltage restoration.
The loss of generation from the wind farm during fault varies from 0 to 100% of the wind farm
capacity. In terms of loss of generation, the benefit of wind power generation is the amount of power
Pad
transformer
Main
substation
Monitoring
node
Wind
turbine
Collector
system
Transmission
line
Infinite
bus
FIGURE 7.13 Typical network topology of a large wind farm.
 
Search WWH ::




Custom Search