parameters, applied for representation of these
states. Selection of such compliance is performed
on the basis of signal receiver properties. For ex-
ample, for execution of protective action initiated
by command of the reactor protection I&C system
(dropping of all control rods into core that causes
emergency shutdown of reactor), outputs of reac-
tor group and individual control rod system are
transferred by this command and retained in active
logical condition that is complied with a lack of
current in circuits, connecting these outputs with
all control rod drives. In the absence of a command
of emergency protection, logical state of outputs
provides direct current in these output circuits.
Safety systems support features that perform
information functions of monitoring, warning, dis-
play, archiving and control functions of regulation,
locking, discrete and remote control described in
Chapter 1. As an example the automatic control
system of diesel-generator used at Ukrainian NPP
(see Belohin et al, 2010) can be given.
During power unit operation or in standby
modes, automatic control system of diesel-
generator:
In case of operational events, the automatic
control system of diesel-generator forms and is-
sues control signals, providing:
• Start-up of a diesel-generator by a com-
mand obtained from the safety protection
I&C system and operational personnel, in-
cluding required operations and further au-
tomatic mutual synchronization of rotation
speed of two diesel-generators, operating
into a total load.
• Automatic support of required parameters
of a diesel-generator during a long period
of time, operating at a full capacity, includ-
ing reill of the service tanks of fuel, oil,
coolant, etc.
• Execution of manual (remote) control
commands: changing of active and reac-
tive generator power, connection and dis-
connection of auxiliary equipment.
• Automatic emergency shutdown of a die-
sel-generator (with locking of the next
launch) in case of actuation of uninter-
ruptable protective means of technological
equipment (other protective means are dis-
connected in order that functions of safety
system support features had a priority over
equipment protection functions).
• Automatic shutdown of a diesel-generator
by a command obtained from personnel,
including operations, which provide avail-
ability of a diesel-electric unit for the next
start-up.
• Warning of personnel (indicating alarm)
about execution of start operation, opera-
tion at a capacity and shutdown.
Supports Diesel: Generator in con-
stant readiness for start-up and fast load
acceptance.
Provides periodic checks (testing) of each
diesel-generator at zero load and with a
load on the a unit electrical network (in-
cluding synchronization of shaft speed
with network frequency and change of gen-
erator reactive capability).
Continuously controls technical state and
diagnoses operability failure of its own
components, adjacent peripheral equip-
ment and connecting lines, archives di-
agnostic results and transfers them to the
main control room for display and warning
of personnel about failures, which can lead
to the system unavailability for execution
of speciied functions.
Continuous monitoring, archiving, dis-
play and register of parameters of a diesel-
generator, adjacent equipment, events and
conditions during operation of a diesel
generator.