Cycle time of data input from sensors and
other I&C systems (SHC).
of a control signal at the input of an actuat-
ing system or an element of technological
equipment (except those commands, which
should be generated with a speciied lag).
• Execution of Remote Control Commands:
Not more than 0,1 sec from the moment of
signal generation at the output of a manual
control key before occurrence of a control
signal at the input of a proper actuating ele-
ment of technological equipment.
• Warning of personnel and display of data
about dangerous initiating events, vio-
lations of design limits and conditions,
changes of monitored parameters and state
of technological equipment, actuation of
safety control systems and normal opera-
tion systems - not more than 1,0 seс from
the moment of occurrence (change) till ac-
tuation of preventive or emergency alarm
at workplaces of personnel and occurrence
of a relevant information in the speciied
format of a data display device.
• Notiication of personnel about operabil-
ity failures, which afect safety, - not more
than 10 seс (other - not more than 1 min)
from failure occurrence till actuation of
preventive alarm at workplaces.
• Archiving of data about initiating events,
violations of design limits of safety op-
eration, occurrence of conditions of gen-
eration protective action commands - 0,01
seс, data of a state of technological equip-
ment, values of monitored parameters and
set-points, violations of operational limits
and conditions, commands of restriction,
regulation, technological protection and
interlocking, discrete and remote control
- 0,1 seс between a time point of event oc-
currence and a time point at which it would
be registered in a data base and an archive.
Time resolution during data input and
archiving.
Lag of performance of discrete function.
Speed of function execution.
Rate of exchange through communication
lines and local networks.
Time of information storage in a data base
and an archive.
Time of start actuation after power
restoration.
Nominal value of time resolution during data
input and archiving are determined for accurate
differentiation and registration of a sequence of
initiating events, changes of state of technological
equipment and controlled parameters, actions of
control systems and personnel in an archive (for
further analysis and estimation):
For information of initiating events, viola-
tions of design limits of safety operation,
occurrence of conditions of initiation of
safety control systems, commands of pro-
tective actions - not worse than 0,01 sec.
For information of a state of technological
equipment, values of monitored parameters
and set-points, violations of operational
limits and conditions, commands of limi-
tation, regulation, technological protection
and interlocking, discrete and remote con-
trol - not worse than 0,1 sec.
Lags of performance of discrete functions
(maximal permissible upper values):
• Output of Protection Commands: Not
more than 0,1 seс, commands of limita-
tion and interlocking - not more than 0,1
seс from a moment of an occurrence of a
design speciic condition till an occurrence
Sampling on an operator call and display
of information from a data base or an ar-