Environmental Engineering Reference
In-Depth Information
Fig. 12.13 RMS-values of
tower deflection of onshore
reference wind turbine with
and without TMD
frequency spectra. TMD can suppress especially the resonant vibrations. There-
fore, the efficiency of TMD at cut-in wind speed is much higher than at rated and
cut-out speeds.
The efficiency of the TMD is evaluated by means of RMS-values of the turbine
tower displacement in fore-aft direction. From the results with and without TMD, a
reduction factor is calculated using Eq. 12.18 . This factor is equivalent to the
vibration energy, which is dissipated by TMD. From the total 1,000 s simulation
time of the turbine response, the last 600 s is used for evaluation. Hereby, the
specified time step of the simulations equals 0.0125 s. To eliminate the static
tower deflection, which cannot be reduced by TMD, a high-pass filter is applied
with a cutoff frequency at 0.1 Hz.
R ¼ 1 RMS with TMD
RMS without TMD
ð 12 : 18 Þ
Figure 12.13 shows the resulting RMS-values. Figure 12.14 shows the differ-
ence between the RMS-values with and without TMD. The reduction factors for
the analyzed wind speeds can be found in Fig. 12.15 . As these graphs also sum-
marize, the designed TMD mitigates the vibrations of the reference wind turbine,
especially at wind speeds lower than 5 m/s. The reduction factor varies between 20
and 80 % (Fig. 12.15 ). At higher wind speeds, the tower vibrations are reduced
slightly by means of the additional structural damping caused by TMD. Hereby,
the reduction factor varies between 5 and 20 % (Fig. 12.15 ).
12.4.3.2 Onshore Reference Wind Turbine with a Tuned Liquid
Column Damper
As described in Sect. 12.3.4.2 by means of the analogy, similar results can also be
obtained using TLCD [ 4 ]. Table 12.7 lists the calculated optimum parameters of
TLCD. Hereby, the active damper mass is, as for TMD, about 5 %. For the chosen
Search WWH ::




Custom Search