Environmental Engineering Reference
In-Depth Information
As shown in Fig. 1.2 , the grid-side converter is connected to the grid through
the filter. The voltage equations for the RL-filter in the dq-synchronous reference
frame can be derived as shown in Sect. 2.6 .
1.2.6 RL-Filter on the Grid-Side Converter
L filt
x b
di dg
dt ¼ v d1 R filt i dg þ x e L filt i qg
ð 1 : 8 Þ
L filt
x b
di qg
dt ¼ v q1 R filt i qg x e L filt i dg
where subscript filt stands for filter.
1.2.7 Voltage Source Converter Controller
Figure 1.4 presents the detailed block diagram of the VSC controller depicting the
respective input and output variables. Here, P set
g is the set-value for the active
power for the WT terminal. The value of P se g is determined from the WT energy-
harvesting characteristic as shown in Fig. 1.5 , which is represented here as a
lookup table P se g ð x r Þ determined in terms of generator rotational-speed x r . Since
variable-speed WTs are traditionally operated in PFC mode to achieve the unity
power factor at the terminal of the WT, the reactive power set-point Q set
g
is set to
zero.
The VSC control module consists of the generator-side, the dc-link, and the
grid-side converter controller. These controllers utilize proportional-integral (PI)
controllers. These PI controllers are tuned using the Nyquist constraint technique
to deal with model uncertainties [ 21 , 22 ]. Each of the controllers is briefly
described below.
v dq,g
v dq,s
v dc
v dc
Q g set
P g set
Q s set
Grid-side
controller
Generator-side
controller
DC-link
controller
set
i dq,g
P s
P s set
v dc ref v dq,g
i dq,g
P g
Q s
i dq,s
ω e
ψ dq,s
L filter
ω e
Fig. 1.4
Block diagram of the VSC controller showing the input/output variables
 
Search WWH ::




Custom Search