Crack width is checked using Equation (8-9) of ACI 440.1R-06. A crack
width limit, w lim , of 0.020 in. is used for exterior exposure:
w lim = 0.02·in.
Crack width limit
FRP ultimate design properties: The ultimate design properties are cal-
culated per Section 7.2 of ACI 440.1R-06:
f fu := C E ·f fuu = 49·ksi
Design tensile strength
ε fu := C E ·ε fuu = 0.0086
Design rupture strain
FRP creep-rupture limit stress: The FRP creep-rupture limit stress is cal-
culated per Section 8.4 of ACI 440.1R-06:
f f _ creep := k creep ·f fu = 9.8·ksi
Minimum FRP reinforcement ratio: The minimum FRP reinforcement
ratio, ρ f,smin , to limit cracks due to shrinkage and temperature is given by
Equation (10-1) of ACI 440.1R-06 (computed in step 3):
ρ fsmin := ρ f _ ts = 0.0036
The following minimum clear concrete cover is selected:
c c := 2.0 in.
The effective reinforcement depth is
3
⋅φ
f_bar
d: hc
=−−
= inf
.
c
f
2
As a starting point for the design, the FRP reinforcement area can be
taken equal to 1.5 times the minimum FRP reinforcement area:
Af_ f_min := (b·d f )·1.5ρ fsmin = 17. 0 85·in. 2
The number of FRP bars can be estimated as follows:
A
A
f_min
N
:
=
=
13.487
barEstimated
f_bar
The number of bars is therefore:
N bar := 14
A f := N bar ·A f_bar = 17.735·in. 2