Crack width is checked using Equation (8-9) of ACI 440.1R-06. A crack
width limit, w
lim
, of 0.020 in. is used for exterior exposure:
w
lim
= 0.02·in.
Crack width limit
FRP ultimate design properties:
The ultimate design properties are cal-
culated per Section 7.2 of ACI 440.1R-06:
f
fu
:= C
E
·f
fuu
= 49·ksi
Design tensile strength
ε
fu
:= C
E
·ε
fuu
= 0.0086
Design rupture strain
FRP creep-rupture limit stress:
The FRP creep-rupture limit stress is cal-
culated per Section 8.4 of ACI 440.1R-06:
f
f
_
creep
:= k
creep
·f
fu
= 9.8·ksi
Minimum FRP reinforcement ratio:
The minimum FRP reinforcement
ratio, ρ
f,smin
, to limit cracks due to shrinkage and temperature is given by
Equation (10-1) of ACI 440.1R-06 (computed in step 3):
ρ
fsmin
:= ρ
f
_
ts
= 0.0036
The following minimum clear concrete cover is selected:
c
c
:= 2.0 in.
The effective reinforcement depth is
3
⋅φ
f_bar
d: hc
=−−
= inf
⋅
.
c
f
2
As a starting point for the design, the FRP reinforcement area can be
taken equal to 1.5 times the minimum FRP reinforcement area:
Af_
f_min
:= (b·d
f
)·1.5ρ
fsmin
= 17. 0 85·in.
2
The number of FRP bars can be estimated as follows:
A
A
f_min
N
:
=
=
13.487
barEstimated
f_bar
The number of bars is therefore:
N
bar
:= 14
A
f
:= N
bar
·A
f_bar
= 17.735·in.
2