The ratio of depth of neutral axis to reinforcement depth, calculated per
Equation (8-12) of ACI 440.1R-06, is
k f = 0.122
The concrete two-way capacity to resist punching shear is from Equation
(9-8a) of ACI 440.1R-06:
5
2 k4 fpsi
(
)
(
)
V =
′ ⋅
bmin d,d=26.04 kip
c1
c
01
f
f1
f2
The concrete shear capacity per unit width, V c , has a minimum value is
1.6
per Chapter 4; therefore:
fbd
co
(
)
(
)
V:=1.6
fpsi
′ ⋅
bmin d d
=34.2kip
c1min
c
01
f1
f2
ϕV n1 := ϕ v ·V c1min = 25.647·kip
“O K” if VV
≤φ
u1
n1
Check_PunchingShear1:=
“Not good”otherwise
Check_PunchingShear1 = “Not good”
For example, including a drop panel at the corner columns could be a solu-
tion to prevent punching shear failure.
8.10.2 Check at column B1
The area of influence is
A I2 := (0.45·1 1 )·(0.5·1 2 ) - b col 2 = 126.822·ft 2
The factored shear force is
V u2 := A I2 ·TFL = 35.4·kip
The perimeter of critical section is
(
)
b =2 b+ mind ,d
2
(
)
(
)
f1
f2
+b +min d,d 73 in
.
02
col
col
f1f 2