Table 17.1 Comparison of current controllers in the grid-connected mode
without a local load
Controller
Current i a THD [%]
Grid voltage v ga THD [%]
H repetitive
1 . 03
1 . 57
PR
3 . 84
1 . 45
PI
4 . 38
1 . 52
DB
3 . 65
1 . 61
The current controllers discussed in Chapters 3 and 15-17 were compared and their cor-
responding values of THD of the grid current are listed in Table 17.2. It can be seen that the
current H repetitive controller considerably outperformed the other controllers.
17.3.1.3 With an Unbalanced Load
In this experiment, an unbalanced resistive local load with R A =
12
, R B =∞
and
was connected to the system. The grid output current reference I d was set at
2 A (after connecting the inverter to the grid) and the reactive power was set at 0 Var ( I q
R C =
12
0).
The output current i a , reference current i ref and the corresponding current tracking error e i in
the steady state are shown in the left column of Figure 17.4. The tracking performance of the
controller remained satisfactory.
The current controllers discussed in Chapters 3 and 15-17 were compared and their cor-
responding values of THD of the grid current are listed in Table 17.3. It can be seen that the
current H repetitive controller considerably outperformed the other controllers.
=
17.3.1.4 With a Non-linear Load
In this experiment, a three-phase uncontrolled rectifier loaded with an LC filter L
=
150
μ
H,
C
was connected to the system. The grid output current
reference I d was set at 2 A (after connecting the inverter to the grid) and the reactive power
was set at 0 Var ( I q
=
1000
μ
F and a resistor R
=
20
0). The output current i a , reference current i ref and the corresponding
current tracking error e i in the steady state are shown in the right column of Figure 17.4. The
tracking performance worsened and the current THD increased considerably.
The current controllers discussed in Chapters 3 and 15-17 were compared and their cor-
responding values of THD of the grid current are listed in Table 17.4. The THD of the grid
current obtained by the current H repetitive controller is below one-third of those obtained
from the other current controllers.
=
Table 17.2 Comparison of current controllers in the grid-connected mode with a
resistive local load
Controller
Current i a THD [%]
Grid Voltage v ga THD [%]
H Repetitive
1 . 53
1 . 63
PR
5 . 79
1 . 41
PI
4 . 93
1 . 41
DB
5 . 8
1 . 59
 