Environmental Engineering Reference
In-Depth Information
If islanding is to be permitted, then the system must be designed to be capable of operating
both grid-connected and standalone. Generally speaking, the standalone mode is the more
diffi cult to engineer since it must include generation/load matching in order to ensure that
voltage and frequency are kept between acceptable limits. Generators that are designed to
operate both grid-connected and standalone are often called standby generators and are
installed primarily to provide security of supply to particularly important loads, such as hos-
pitals and computer centres. Standby generators are usually powered from diesel or gas.
Systems employing renewables are rarely designed to operate both grid-connected and
standalone. The extra cost of properly engineering a standalone mode is unlikely to be justi-
fi ed unless grid power cuts are very frequent.
If a generator is not designed to operate in a standalone mode, it must be capable of shut-
ting down immediately when the grid connection is lost, otherwise the system may become
dangerous for the following reasons:
￿ The island may not be properly earthed and may present an electric shock hazard to
personnel.
￿ A system that appears to be disconnected from the mains but is in fact still live also presents
a shock hazard.
￿ The voltage and/or frequency may deviate from the normal range and this may damage
other equipment connected within the island.
￿ The island's frequency will quickly deviate from that of the main network and if the two
networks are reconnected under these circumstances, equipment (particularly synchronous
machines) will probably be damaged.
￿ The fault level within the island will be reduced and, if a fault were to develop, the result-
ing current might be insuffi cient to operate protective devices such as circuit breakers and
fuses decisively.
6.5.2 Loss - of - mains Protection for Rotating Machines
Satisfactory loss - of - mains detection is surprisingly diffi cult to achieve with rotating machines.
The detection must be reliable, fast and stable and not prone to wrong tripping. The require-
ment that it must be fast stems from the widespread use of auto - reclose circuit breakers in
distribution systems and from the fact that these are not normally fi tted with synchronization
checking. Auto-reclosers are designed to restore a supply very quickly after a transient fault.
Most faults in distribution systems (upwards of 80%) are transient and thus reclosers play a
very important role in reducing customer-minutes lost. Reclose times in distribution systems
can be as short as 1 second, which is good for consumers but also implies that loss-of-mains
protection must be designed to operate well within 1 second.
For small induction generators, under/overvoltage and under/overfrequency protection is
considered adequate protection against loss-of-mains (in the UK). For synchronous generators
and large induction generators the preferred loss-of-mains detection techniques are:
￿ rate of change of frequency (ROCOF) and
￿ vector shift.
Search WWH ::




Custom Search