Civil Engineering Reference
In-Depth Information
of both horizontal and vertical reinforcing, as described in Section 11.10.9 or
Chapter 14 of the Code.
9.
Should
V
u
be greater than
V
c
/2, shear wall reinforcing must be designed as de-
scribed in Section 11.10.9 of the Code.
10.
If the factored shear force
V
u
exceeds the shear strength
V
c
, the value of
V
s
is to
be determined from the following expression, in which
A
v
is the area of the hori-
zontal shear reinforcement and
s
2
is the spacing of the shear or torsional reinforc-
ing in a direction perpendicular to the horizontal reinforcing (11.10.9.1).
A
v
f
y
d
V
s
(ACI Equation 11-31)
s
2
11.
The amount of horizontal shear reinforcing
h
(as a percent of the gross vertical
concrete area) shall not be less than 0.0025 (11.10.9.2).
12.
The maximum spacing of horizontal shear reinforcing
s
2
shall not be greater than
w
/5, 3
h
, or 18 in. (11.10.9.3).
13.
The amount of vertical shear reinforcing
n
(as a percent of the gross horizontal
concrete area) shall not be less than the value given by the following equation, in
which
h
w
is the total height of the wall (11.10.9.4).
h
w
w
n
0.0025
0.5
2.5
(
h
0.0025)
(ACI Section 11-32)
It shall not be less than 0.0025 but need not be greater than the required horizon-
tal shear reinforcing
h
.
For high walls, the vertical reinforcing is much less effective than it is in
low walls. This fact is reflected in the preceding equation, where for walls with a
height/length ratio less than 0.5, the amount of vertical reinforcing required
equals the horizontal reinforcing required. If the ratio is larger than 2.5, only a
minimum amount of vertical reinforcing is required (that is 0.0025
s
1
h
).
14.
The maximum spacing of vertical shear reinforcing
s
1
shall not be greater than
w
/3, 3
h
, or 18 in. (11.10.9.5).
EXAMPLE 18.2
c
Design the reinforced concrete wall shown in Figure 18.6 if
f
3000 psi and
f
y
60,000 psi.
Figure 18.6