For 22-ft interior beam (with 18-ft slab width)
1
12
(12 18)(6) 3 3888 in. 4
I s
15,870
3888
4.08
5.36 3.34 (2)(4.08)
4
m
Avg.
4.21
s ratio of length of continuous edges to total perimeter
62
80
0.78
ratio of long to short clear span 22 1 12
18 1 12
1.24
(e)
Thickness limits by Code Section 9.5.3
n 22.0 15
12 20.75 ft
As m 2.0, use ACI Equation 9- 13.
f y
200,000
n
0.8
h
36 9
0.8 60,000
200,000
(12)(20.75)
5.81 in. k
36
(9)(1.24)
h not less than 3.5 in. (as per ACI Section 9.5.3.3(c))
Try h
6 in. (shear checked later)
3. Moments for the short-span direction centered on interior column line:
w u
(1.2)(100)
(1.6)(120)
312 psf
M o ( w 2 )( n ) 2
8
(0.312)(22)(16.75) 2
8
241 ft- k
(a) Dividing this static design moment into negative and positive portions, as per Section
13.6.3.2 of the Code:
negative design moment (0.65)(241) 157 ft- k
positive design moment (0.35)(241) 84 ft- k
(b) Allotting these interior moments to beam and column strips, as per Section 13.6.4 of
the Code:
2
22
1
18
1.22
1 in direction of short span 3.34
1 2
1 (3.34)(1.22) 4.07
The portion of the interior negative moment to be resisted by the column strip, as per Table
16.3 of this chapter, by interpolation is (0.68)( 157) 107 ft-k. This 107 ft-k is allotted 85%