8 ' 0 "
7 ' 0 "
P.I.
P.I.
moment capacity with 2 bars
moment capacity with 4 bars
moment capacity with 6 bars
55 "
23 "
18 "
16 "
20 "
48 "
48 " + half
support
width
48 " + half
support
width
"bottom" 2 bars
"middle" 2 bars
18 " + 54 " = 6 ' 0 "
16 " + 54 " = 5 ' 10 "
1
2
1
2
18 " + 23 " + 55 " + 24 " = 10 ' 0 "
16 " + 20 " + 48 " + 25 " = 9 ' 1 "
"top" 2 bars
Figure 14.36
Assume K tr 0
(1.3)(1.0)(1.0)(1.0)
2.0 0
1.0
d
60,000
3
40
d b
53.4 diameters
3000
d
(53.41)(1.0)
53.4
Say 54
OK
2. Section 12.12.3 of the Code requires one-third of the bars to extend beyond P.I. (1/3
6
2 bars) for a distance equal to the largest of the following values (applies to “top” bars in figure).
(a)
d of web
24
(b) 12 d b
(12)(1)
12
(c)
( 16 )(24
12)
for 24
span
18
( 16 )(34
12)
for 34
span
25 2
Use 24 for short span and 25 2 for long span
3. Section 12.10.3 of the Code requires that the bars shall extend beyond the point where they
are no longer required by moment for a distance equal to the greater of:
(a)
d
24
(b) 12 d b
(12)(1)
12