2. Is it a slender column?
9
u
12
12
11.25 ft
Max k u
4
to be a short column 22 for nonsway frames.
k u
r
(1.95)(12 11.25)
0.3 12
73.12 22
It is a slender column
3. Consider the loading case U 1.2D 1.6L ( See Figure 11.10 ).
a.
Are column moments ACI minimum?
e min 0.6 0.03 12 0.96 in.
M 2,min (66)(0.96) 63.36 in.- k 5.28 ft- k 173.5 ft- k
(see Figure 11.10)
OK
b.
Compute the magnification factor ns :
E c 57,000 4000 3,605,000 psi 3605 ksi
(1.2)(1)
(1.2)(1) (1.6)(2)
d
0.273
(0.4)(3605)(1210)
1 0.273
EI
1.37
10 6 k-in. 2
Figure 11.10