Figure 5.4
Calculating a , c , and t
a 105.88
60
1.76 in.
c a
1 1.76
0.85 2.07 in.
d c
c
24 2.07
2.07
t
(0.003)
(0.003)
0.0318 0.005
Section is ductile and 0.90
Calculating M n
Obviously, the stress block is entirely within the flange, and the rectangular formulas apply.
However, using the couple method as follows:
Lever arm z d a
2 24 1.76
23.12 in.
2
M n T z (0.90)(360)(23.12)
7490.9 in.- k 624.2 ft- k
EXAMPLE 5.2
c
Compute the design strength for the T beam shown in Figure 5.5 in which
f
4000 psi and f y
60,000 psi.
SOLUTION
Checking A s min
3 4000
60,000
A s min
(14)(30)
1.33 in. 2
nor less than (200)(14)(30)
60,000
1.40 in 2 k
A s 10.12 in. 2
OK