Switch off one pump
System curve
Switch on one pump
Pump curve
(3 pumps)
(1 pump)
(2 pumps)
Water flow rate
Figure 9.23 Settings of sequence control of constant-speed secondary chilled water
pumps based on differential pressure.
Pump pressure
Throttling
Reducing speed
C
Differential pressure
set-point
A
B
Pump curve
System Curve
m2
m1
Flow rate
Figure 9.24 Control of variable-speed pump with pre-set differential pressure across
the critical load branch.
In the strategy illustrated in Figure 9.23, a lag is specified to avoid the cycling
on/off of pumps and the flow rates at switching on points are slightly higher
that that of relevant switching off points.
 