air flow to the air-conditioned zones. In cases where pneumatic controllers
are used for VAV boxes or the VAV controllers are not integrated with the
AHU controllers, it is not possible for the AHU controller to have the infor-
mation on the control of VAV boxes, so some 'near optimal' control could be
adopted. The optimal set-point can be set as a function of the total supply air
flow rate according to experience or site monitoring or site tests. When the
total supply air flow rate reduces, the pressure set-point can be reduced.
8.6.2 Supply air temperature set-point reset
The air flow rate to a zone is reduced by closing down the VAV damper when
the load of a zone is low. Under low partial load, the total flow rate of a
zone may be reduced to be very low in order to meet the reduced load. The
reduction in total flow rate results in significant savings in fan power. On
the other hand, a low ventilation flow rate may cause deficiencies in system
performance (e.g. poor mixing of supply air and room air, inadequate room
ambient air circulation and dumping). When a minimum limit of the total
flow rate is used, a space may be overcooled under low partial load if the
supply air temperature is low.
A proper resetting of the supply air temperature allows the VAV system to
avoid poor ventilation and save fan power. A strategy for online reset of the
supply air temperature set-point is illustrated in Figure 8.29. The strategy
utilizes the air flow rate set-points of the pressure-independent VAV box
VAV damper
Supply
Return
Occupied zone
F
T
A
Air flow
set-point
AHU supply air
temperature set-point
Air flow
controller
Temperature
controller
From other
zones
AHU supply air temperature set-point reset
Ratio to high
flow setting
M up,set
H PID
Maximum
PID (-)
Function
Change rate
limit
N max
N min
Ratio to low
flow setting
PID (-)
Function
Minimum
Re-scale
M min,set
From other
zones
L PID
RM min,H
RM min,L
RM min,set
RM min,hys
Threshold
settings
PID (+)
Function
Differential
Figure 8.29 Schematic of AHU supply air temperature set-point reset strategy.
 