Civil Engineering Reference
In-Depth Information
The best location is on the windward side of the building.
Intakes should be located in the lower third of the wall, with the
bottom of the intake approximately 2 feet above grade. (For indus-
trial applications, hospitals, and research facilities, where hazardous
exhaust discharge is required, special care must be taken to ensure
that re-entry of pollutants does not take place.)
Outside air intakes must be separated from any potential pollutant
source in accordance with Table 4-9.
Table 4-9. Minimum Air Intake Separation Requirements
————————————————————————————————
MinimumDistance(ft)
————————————————————————————————
General building exhaust 5
Significantly contaminated exhaust or vents 15
Noxious or dangerous exhaust or vents* 30
Garage entry, automobile loading area, or drive-in queue 15
Truck loading area or dock, bus parking/idling area 25
Driveway, street or parking place 5
Thoroughfare with high traffic volume 25
Roof, grade, or other surface directly below intake 1
Garbage storage/pick-up area, dumpsters 15
Cooling tower intake or basin 15**
Cooling tower exhaust 25**
————————————————————————————————
*Laboratory fume hood exhaust air outlets shall be in compliance with NFPA 45 and ANSI/
AIHA Z9.5.
**This distance should be a great as possible to reduce Legionella contamination potential.
Object
Filters are applied in air-handling systems to remove particulate
contaminants and pollutants such as dust, pollen, mold, bacteria, smoke,
and etc. from the air. ASHRAE Standard 52.2-2007 defines the method-
ology of rating and applying filters in HVAC systems by establishing
minimumeficiencyratingvalues(MERV) for filters and a test method for
determining the MERV. Table 4-10 summarizes the application guidelines
for each type of filter and establishes a range of recommended MERVs.
This table can be used to select air cleaner performance required for most
HVAC applications.
“Electrostatic filters,” passive residential grade filters, are ranked at
Search WWH ::