Environmental Engineering Reference
In-Depth Information
TABLE 7.14 (CONTINUED)
TES Building Applications
Temperature
(°C)
Application
StorageMedium
Type
Bulk form-stable
cross-linked
polymer PCM,
direct HX
Latent
Cold side storage
for Rankine, liquid
absorption, and
zeolite chillers
5 to 10
Water in naturally
stratified tank
Sensible
Water in multiple,
partitioned, or
flexibly divided
tanks
Sensible
Encapsulated PCM
Latent
Bulk PCM with
indirect HX
Latent
Bulk PCM with
direct HX and
immiscible fluid
Latent
Open cycle systems
(dessicant chillers)
90
Rock beds for solid
adsorption
systems
Sensible
60
Strong salt solution
TC
Space heating and
cooling
(thermochemical
heat pumps with
reactant storage)
100 to 130
Intermittent
solid-vapor
systems
Latent
Continuous or
intermittent
liquid-vapor
systems
Latent
Domestic Hot Water
Naturally stratified
deliverable water
in thermocline tank
55
Supplementary
PCM encapsulated
bulk between
double walls of
water tank
Latent
Source:
de Winter, F. 1990. Solar Collectors, Energy Storage, and Materials , MIT
Press, Cambridge, MA. With permission.
heat stores also use soil to store heat, but employ active mechanisms of solar
collection in summer to heat thermal banks in advance of the heating season
[14]. High temperature seasonal heat stores are essentially extensions of a
building's heating, ventilation, air conditioning, and water heating systems.
Water is normally the storage medium, stored in tanks at temperatures that
 
Search WWH ::