Cause: Chlorine residual is too low
Corrective action: Increase contact time and/or increase chlo-
rine feed rate.
symptom 2.
Chlorinator has low chlorine gas pressure.
Cause: Insufficient number of cylinders connected to the system
Corrective action: Connect enough cylinders to the system so
the feed rate does not exceed recommended withdrawal rate for
cylinders.
Cause: Stoppage or restriction of flow between cylinders and
chlorinator
Corrective action: Disassemble the chlorine header system at
the point where cooling begins, locate the stoppage, and clean
with solvent.
symptom 3.
Chlorinator has no chlorine gas pressure.
Cause: Empty chlorine cylinders or cylinders not connected to the
system
Corrective action: Replace the empty cylinders or connect the
cylinders.
Cause: Plugged or damaged pressure-reducing valve
Corrective action: Repair reducing valve after shutting cylinder
valves and decreasing gas in the header system.
symptom 4.
Chlorinator will not feed any chlorine.
Cause: Dirty pressure-reducing valve in the chlorinator
Corrective action: Disassemble the chlorinator and clean the
valve stem and seat; precede the valve with a filter/sediment
trap.
Cause: Chlorine cylinder hotter than the chlorine control appara-
tus (chlorinator)
Corrective action: Reduce the temperature in the cylinder area;
do not connect a new cylinder that has been sitting in the sun.
symptom 5.
Chlorine gas is escaping from the pressure-reducing
valve.
Cause: Ruptured pressure-reducing valve main diaphragm
Corrective action: Disassemble the valve and diaphragm; inspect
the chlorine supply system for moisture intrusion.
symptom 6.
Chlorine feed rate cannot be maintained without icing
of the chlorine system.
Cause: Insufficient evaporator capacity
Corrective action: Reduce feed rate to 75% of evaporator capacity;
if this eliminates the problem, then the main diaphragm of the
pressure-reducing valve is ruptured.
Cause: The external pressure-reducing valve cartridge is clogged
Corrective action: Flush and clean the cartridge.