Table 18 Inverter technical data
Output voltage
Battery voltage
Charge current
Maximum current
Power
230 V
AC
/50 Hz
48 V
DC
50 A
DC
50 A
AC
4,000 VA
For sizing the inverters the following conditions were satis
ed:
Rated output capacity of inverter P
output
> P
CHP
/3, resulting P
output
= 3 kW;
Input voltage inverter V
input
= V
CC
= 48 V (equal with the rated batteries
voltage);
Rated output voltage V
output
= 220 ~ 230, V
AC
50
±
0.05 Hz, THD < 4 %.
The inverters chosen have perfect sine wave output [
12
] with technical data
shown in Table
18
and the schematic diagram presented in the Fig.
14
.
In addition to the output wave type, the main features of the inverter are:
Inverters have a higher ef
ciency near the rated power so that the operating
recommendation is close to the nominal load. Usually, the manufacturer gives
the inverters performance to a 70 % load of rated power;