Table 18 Inverter technical data
Output voltage
Battery voltage
Charge current
Maximum current
Power
230 V AC /50 Hz
48 V DC
50 A DC
50 A AC
4,000 VA
For sizing the inverters the following conditions were satis
ed:
Rated output capacity of inverter P output > P CHP /3, resulting P output = 3 kW;
￿
Input voltage inverter V input = V CC = 48 V (equal with the rated batteries
voltage);
￿
Rated output voltage V output = 220 ~ 230, V AC 50
±
0.05 Hz, THD < 4 %.
￿
The inverters chosen have perfect sine wave output [ 12 ] with technical data
shown in Table 18 and the schematic diagram presented in the Fig. 14 .
In addition to the output wave type, the main features of the inverter are:
Inverters have a higher ef
ciency near the rated power so that the operating
recommendation is close to the nominal load. Usually, the manufacturer gives
the inverters performance to a 70 % load of rated power;
￿
Fig. 14 Internal diagram of the inverter [ 12 ]